Chapter 7 Example Explanation|ScrEdit Software User Manual
Revision Apr. 30th, 2007, 2007PDD23000002 7-5
Select the Edit On Macro
In the Macro section type in (2@INVERTER-2000) = 2
This will cause the Drive to turn on when the button is selected.
The screen will look like Fig. 7.6.
Fig. 7.6
Go to the Screen drop down and at the bottom select Screen Cycle Macro
Type in (2@INVERTER-0200) = 3
Type in (2@INVERTER-0201) = 4
This set’s up the drive to accept control from the HMI via RS485 communication.
In the Screen Cycle Macro the user must set-up the Drive to accept the commands coming from the
HMI.
The screen will look like Fig. 7.7.