5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-51
06-16
Op stall low limit
a
Factory setting 120
Settings 0~250%
06-17 Most Recent Fault Record Factory setting 0
06-18 2
nd
Most Recent Fault Record Factory setting 0
06-19 3
rd
Most Recent Fault Record Factory setting 0
06-20 4
th
Most Recent Fault Record Factory setting 0
Content 0 no fault
displayed 1 oc (over-current)
2 ov (over-voltage)
3 oH1 (IGBT overheat)
4 oL (drive overload)
5 oL1 (electronic thermal relay)
6 EF (external fault)
7 CF3 (hardware circuit fault)
8 HPF (protection circuit fault)
9 ocA (over-current during accel)
10 ocd (over-current during decel)
11 ocn (over-current during constant speed)
12 GFF (ground fault)
13
pg error
14
Lv (low voltage)
15
CF1 (unable to write to memory)
16
CF2 (unable to read memory)
17
bb (Pause)
18
oL2 (motor overload)
19
sc (IGBT failure)
20
brake (braking transistor failure)
21 OL3 (motor overload)
22
oh2 (brake overheat)
23
Fuse failure
24
CT2 (current sensor 2)
25
CT1 (current sensor 1)
26
PWM (upper and lower points at the same low level)
27
Motor auto tuning failure