Chapt er 6 Troubles h o o ting
6-9
6.4 Basic Inspection of DVP04PT-S and Error Code
Table
Checking the wiring
1. Check whether the module is connected to 24 V power, and check whether the POWER
LED indicator on the module is turned ON after the module is supplied with the power.
2. Do not connect input AC power supply to any of the I/O terminals, otherwise serious
damage may occur. Check all the wiring again before supplying power.
3. Use only the wires that are packed with the temperature sensor for the analog inputs, and
separate the wires from other power cables or any wire that may cause noise.
4. The terminal FG is grounded for noise suppression.
5. Please connect the terminal on the power module and the terminal on the
temperature measurement module DVP04PT-S to the system earth point, and ground the
system earth point or connect it to the machine cover.
Checking the program
1. Check whether the use of the devices in the program is correct.
2. Check whether the setting of the number of values which will be averaged and the related
setting are correct.
CR#30: Please refer to the table below for more information about the error code stored in
CR#30.
Error description Content b15~b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Power source abnormal K1 (H’1)
0
0
0
0
0
0
0
0
0
0
0
1
The contact is not connected
to anything.
K2 (H’2)
0
0
0
0
0
0
0
0
0
0
1
0
Hardware malfunction K16 (H’10)
0
0
0
0
0
0
0
1
0
0
0
0
Average times setting error K64 (H’40)
0
0
0
0
0
1
0
0
0
0
0
0
Instruction error K128 (H’80)
0
0
0
0
1
0
0
0
0
0
0
0
The contact of CH1 is not
connected to anything.
(Abnormal conversion)
K256
(H’100)
0
0
0
1
0
0
0
0
0
0
0
0
The contact of CH2 is not
connected to anything.
(Abnormal conversion)
K512
(H’200)
0
0
1
0
0
0
0
0
0
0
0
0
The contact of CH3 is not
connected to anything.
(Abnormal conversion)
K1024
(H’400)
0
1
0
0
0
0
0
0
0
0
0
0
The contact of CH4 is not
connected to anything.
(Abnormal conversion)
K2048
(H’800)
Reserved
1
0
0
0
0
0
0
0
0
0
0
0
Note: Each error code
will have corresponding bit (b0 ~ b7). Two or more errors may happen at
the same time. 0 means normal and 1 means having error.