VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-52
Command code: 10H, write n word, n<=12
For example, writing 6000(1770H) to Pr 5-00 (address 0500H) and 1000(03E8H) to Pr 5-01
(address 0501H) with slave address 01H.
ASCII mód:
Command message: Response message:
STX ‘:’ STX ‘:’
ADR 1 ‘0’ ADR 1 ‘0’
ADR 0 ‘1’ ADR 0 ‘1’
CMD 1 ‘1’ CMD 1 ‘1’
CMD 0 ‘0’ CMD 0 ‘0’
‘0’ ‘0’
‘5’ ‘5’
‘0’ ‘0’
Starting Data
address
‘0’
Starting Data
address
‘0’
‘0’ ‘0’
‘0’ ‘0’
‘0’ ‘0’
Number of data
(count by word)
‘2’
Number of data
(count by word)
‘2’
‘0’ LRC CHK 1 ‘E’ Number of data
(count by byte)
‘4’ LRC CHK 0 ‘8’
‘1’ END 1 CR
‘7’ END 0 LF
‘7’
Data content of
address 0500H
‘0’
‘0’
‘3’
‘E’
Data content of
address 0501H
‘8’
LRC CHK 1 ‘7
LRC CHK 0 ‘2
END 1 CR
END 0 LF