English- 1
Preface
Thank you for choosing DELTA’s high-performance VFD-E Series. The VFD-E Series is
manufactured with high-quality components and materials and incorporate the latest microprocessor
technology available.
Getting Started
This quick start will be helpful in the installation and parameter setting of the AC motor drives. To
guarantee safe operation of the equipment, read the following safety guidelines before
connecting power to the AC motor drives. For detail information, refer to the VFD-E User Manual
on the CD supplied with the drive.
DANGER!
1.
AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power has
been turned off. To prevent personal injury, please ensure that power has turned off before opening the
AC motor drive and wait ten minutes for the capacitors to discharge to safe voltage levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3
directly to the AC mains circuit power supply.
5. Ground the VFD-E using the ground terminal. The grounding method must comply with the laws of the
country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-E series is used only to control variable speed of 3-phase induction motors, NOT for 1-phase
motors or other purpose.
7. VFD-E series is the specific drive for the elevator door and other automatic door control, NOT for those
devices that may cause personal injury, such as life support equipment or any life safety situation.
8. To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC motor drive is
installed on an ungrounded power system or a high resistance-grounded (over 30 ohms) power system
or a corner grounded TN system.
WARNING!
1.
DO NOT use Hi-pot test for internal components. The semi-conductor used in AC motor drive easily
damage by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components are
especially sensitive to static electricity. To prevent damage to these components, do not touch these
components or the circuit boards with metal objects or your bare hands.
3. Only quality person is allowed to install, wire and maintain AC motor drive.
CAUTION!
1.
Some parameters settings can cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight, high
humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic particles. Only use
AC motor drives within specification. Failure to comply may result in fire, explosion or electric shock. To
prevent personal injury, please keep children and unqualified people away from the equipment.
3. When the motor cable between AC motor drive and motor is too long, the layer insulation of the motor
may be damaged. Please use a frequency inverter duty motor or add an AC output reactor to prevent
damage to the motor. Refer to appendix B Reactor for details.
4. The rated voltage for AC motor drive must be 240V and the mains supply current capacity must be
5000A RMS.
Vedere la pagina 0
1 2 3 4 5 6 ... 35 36

Sommario

Pagina 1 - Preface

English- 1Preface Thank you for choosing DELTA’s high-performance VFD-E Series. The VFD-E Series is manufactured with high-quality components and mat

Pagina 2 - Specifications

English- 10Terminal Symbol Terminal Function Factory Settings (NPN mode) ON: Connect to DCM MO1 Multi-function Output 1 (Photocoupler) Maximum 48VDC,

Pagina 3

English- 11Pr. Explanation Settings Factory SettingNOTE00.01 Rated Current Display of the AC motor drive Read-only #.# 00.02 Parameter Reset 0: P

Pagina 4 - Basic Wiring Diagram

English- 12Pr. Explanation Settings Factory SettingNOTE00.12 50Hz Base Voltage Selection 0: 230V/400V 1: 220V/380V 0 Group 1 Basic Parameters 01.0

Pagina 5 - (optional)

English- 13Pr. Explanation Settings Factory SettingNOTE01.21 Delay Time at 10Hz for Simple Position0.00 to 600.00 sec 0.00 01.22 Delay Time at 20H

Pagina 6 - Signal Description

English- 14Pr. Explanation Settings Factory SettingNOTE01.40 Mid-Point Frequency (Fmid) (Motor 3) 0.10 to 600.0 Hz 1.50 115V/230V series: 0.1V to

Pagina 7 - English- 7

English- 15Pr. Explanation Settings Factory SettingNOTE02.05 Line Start Lockout 0: Disable. Operation status is not changed even if operation comm

Pagina 8 - Terminal Explanations

English- 16Pr. Explanation Settings Factory SettingNOTE02.14 Initial Frequency Selection (for keypad & RS485/USB) 0: by Current Freq Command 1:

Pagina 9 - Terminals 1

English- 17Pr. Explanation Settings Factory SettingNOTE03.05 Terminal Count Value 0 to 9999 0 03.06 Preliminary Count Value 0 to 9999 0 03.07

Pagina 10 - English- 10

English- 18Pr. Explanation Settings Factory SettingNOTE04.03 Keypad Potentiometer Negative Bias, Reverse Motion Enable/Disable 0: No negative bias

Pagina 11 - English- 11

English- 19Pr. Explanation Settings Factory SettingNOTE Bit11:MI12 0:N.O., 1:N.C. P.S.:MI1 to MI3 will be invalid when it is 3-wire control. 04.

Pagina 12 - English- 12

English- 2Specifications Voltage Class 115V Class Model Number VFD-XXXE 002 004 007 Max. Applicable Motor Output (kW) 0.2 0.4 0.75 Max. Applic

Pagina 13 - English- 13

English- 20Pr. Explanation Settings Factory SettingNOTE Bit8: MI9 Status Bit9: MI10 Status Bit10: MI11 Status Bit11: MI12 Status 04.27 Internal/

Pagina 14 - English- 14

English- 21Pr. Explanation Settings Factory SettingNOTE06.03 Over-Torque Detection Mode (OL2) 0: Disabled 1: Enabled during constant speed operatio

Pagina 15 - English- 15

English- 22Pr. Explanation Settings Factory SettingNOTE 06.11 Fourth Most Recent Fault Record 06.12 Fifth Most Recent Fault Record 27: DC

Pagina 16 - English- 16

English- 23Pr. Explanation Settings Factory SettingNOTE07.15 Motor PTC Overheat Warning Level 0.1~10.0V 1.2 07.16 Motor PTC Overheat Reset Delta L

Pagina 17 - English- 17

English- 24Pr. Explanation Settings Factory SettingNOTE07.36 Motor Line-to-line Resistance R1 (Motor 3) 0~65535 mΩ 0 07.37 Motor Rated Slip (Motor

Pagina 18 - English- 18

English- 25Pr. Explanation Settings Factory SettingNOTE08.17 Auto Energy Saving0: Disable 1: Enable 0 08.18 AVR Function 0: AVR function enable 1

Pagina 19 - English- 19

English- 26Pr. Explanation Settings Factory SettingNOTEa09.08 Transmission Speedfor USB Card 0: Baud rate 4800 bps 1: Baud rate 9600 bps 2: Baud ra

Pagina 20 - English- 20

English- 27Pr. Explanation Settings Factory SettingNOTE10.00 PID Set Point Selection 0: Disable PID operation 1: Keypad (based on Pr.02.00) 2: 0 t

Pagina 21 - English- 21

English- 28Pr. Explanation Settings Factory SettingNOTE11.00 Multi-function Output Terminal MO2/RA2 0 11.01 Multi-function Output Terminal MO3/RA3

Pagina 22 - English- 22

English- 29Pr. Explanation Settings Factory SettingNOTE23: Quick Stop (Only for VFD*E*C models)24: Download/execute/monitor PLC Program (PLC2) (NOT

Pagina 23 - English- 23

English- 3General Specifications Control System SPWM(Sinusoidal Pulse Width Modulation) control (V/f or sensorless vector control) Frequency Setting

Pagina 24 - English- 24

English- 30Pr. Explanation Settings Factory SettingNOTE12.18 Max. ACI3 Input Current 0.0 to 20.0mA 20.0 12.19 Max. ACI3 Scale Percentage 0.0 to

Pagina 25 - English- 25

English- 31Fault Name Fault Descriptions Corrective Actions Low voltage The AC motor drive detects that the DC bus voltage has fallen below its min

Pagina 26 - English- 26

English- 32Fault Name Fault Descriptions Corrective Actions Overload 2 Motor overload. 1. Reduce the motor load. 2. Adjust the over-torque detect

Pagina 27 - English- 27

English- 33Fault Name Fault Descriptions Corrective Actions Auto accel/decel failure 1. Check if the motor is suitable for operation by AC motor d

Pagina 28 - English- 28

English- 34Fault Name Fault Descriptions Corrective Actions CANopen SYNC Time out (Only for VFDxxxExxC) Check if CANopen synchronous message is abn

Pagina 29 - English- 29

English- 35NOTE Frame A (A1): VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A, VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/

Pagina 30 - Fault Codes

English- 36Frame C HH1W1WS1S2DD1D2 Unit: mm [inch] Frame W W1 H H1 D D1 D2 S1 S2 C1 130.0 [5.12] 116.0 [4.57] 260.0[10.24]246.5[9.70]169.2[

Pagina 31 - English- 31

English- 4Storage/ Transportation Temperature -20 oC to 60 oC Ambient Humidity Below 90% RH (non-condensing) Vibration 9.80665m/s2 (1G) less than 20

Pagina 32 - English- 32

English- 5+-Please use brake unit and/or brake resistor depending on type and applicationBra ke un it (optional)BUEBRbrake resistor(opti onal)Figu

Pagina 33 - English- 33

English- 6C. PNP mode without external power D. PNP mode with external power Sw1FactorysettingNPNPNP Sw1FactorysettingNPNPNP 24Vdc-+ Figure 5 RJ-4

Pagina 34 - English- 34

English- 7Operation Steps of the Digital Keypad To s hif t d a taSetting PLC ModeSetting ModeSetting direction(When operation source is digital keyp

Pagina 35 - English- 35

English- 8Power Terminals and Control Terminals Frame AFrame BFrame C Frame Power Terminals Torque Wire Wire Type R/L1, S/L2, T/L3 A U/T1, V/T2,

Pagina 36 - English- 36

English- 9The Specification for the Control Terminals RS-485 port 10VMI1 MI2 MI3 MI4 MI5 MI6DCM24VDCMACMAVI ACIAFM MCM MO1RARB