DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
32
LED status Indication How to correct
voltage 2. Acquire diagnostic information through
DeviceNetBuilder.
Red light on
Fatal error; errors in
configuration data
Acquire diagnostic information through
DeviceNetBuilder.
6.5 RUN LED
LED status Indication How to correct
Off RTU-DNET in STOP mode --
Green light on RTU-DNET in RUN mode --
Appendix A: DeviceNet Objects RTU-DNET Supports
DeviceNet objects
Class Object
0x01 Identity object
0x02 Message router object
0x03 DeviceNet object
0x05 Connection object
0x9A RTU-DNET setup parameter object
0x9B Extension module setup parameter object
0x9C Extension module parameter object
Class 0x01 – Identity object
Class attribute
Attribute ID Access rule Name Data type
1 Get Revision UINT
2 Get MaxInstance UINT
3 Get NumberofInstances UINT
6 Get MaxIdClass UINT
7 Get MaxIdInstance UINT
Instance
Attribute ID Access rule Name Data type
1 Get VendorId UINT
2 Get DeviceType UINT
3 Get ProductCode UINT
4 Get
Revision
MaxRev
MinRev
USINT
USINT
5 Get Status WORD
6 Get Sn UDINT
7 Get
ProdName
StrLen
ASCIIStr
USINT
STRING