Delta-electronics Programmable Logic Controller DVP-PLC Manuale Utente Pagina 317

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 586
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 316
7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-33
Program Example:
When X0 = On, Y1 will output the pulses as below. When X0 = Off, Y1 output will also be Off.
X0
PWM K1000 K2000 Y1
Y1 output
t=1,000ms
T=2,000ms
Remarks:
1. Flags for ES/EX/SS/SA/SX/SC series MPU:
M1070: Y1 pulse output time unit switch. When Off: 1ms; when On: 100us
2. Flags and special registers for EH/EH2/SV series MPU:
M1010: (EH/EH2/SV) When On, CH0, CH1, CH2 and CH3 will output pulses when END instruction is
executed. Off when the output starts.
M1070: (EH/EH2/SV) The setting of time unit of CH0 has to work with D1371.
M1071: (EH/EH2/SV) The setting of time unit of CH1 has to work with D1372.
M1258: (EH/EH2/SV) CH0 pulse output signals reverse.
M1259: (EH/EH2/SV) CH1 pulse output signals reverse.
M1334: (EH/EH2/SV) CH0 pulse output pauses.
M1335: (EH/EH2/SV) CH1 pulse output pauses.
M1336: (EH/EH2/SV) CH0 pulse output has been sent.
M1337: (EH/EH2/SV) CH1 pulse output has been sent.
M1520: (EH2/SV) CH2 pulse output pauses.
M1521: (EH2/SV) CH3 pulse output pauses.
M1522: (EH2/SV) CH2 pulse output has been sent.
M1523: (EH2/SV) CH3 pulse output has been sent.
M1526: (EH2/SV) CH2 pulse output signals reverse.
M1527: (EH2/SV) CH3 pulse output signals reverse.
M1530: (EH2/SV) The setting of time unit of CH2 has to work with D1373.
M1531: (EH2/SV) The setting of time unit of CH3 has to work with D1374.
D1336: (EH/EH2/SV) Low word of the current number of output pulses from CH0.
D1337: (EH/EH2/SV) High word of the current number of output pulses from CH0.
D1338: (EH/EH2/SV) Low word of the current number of output pulses from CH1.
D1339: (EH/EH2/SV) High word of the current number of output pulses from CH1.
D1371: (EH/EH2/SV) Time unit of CH0 output pulses when M1070 = On.
D1372: (EH/EH2/SV) Time unit of CH1 output pulses when M1071 = On.