9 Application Instructions API 150-199
DVP-PLC Application Manual
9-29
D1336:
For EH/EH2/SV, low word of the current number of output pulses from CH0.
D1337:
For EH/EH2/SV, high word of the current number of output pulses from CH0.
D1338:
For EH/EH2/SV, low word of the current number of output pulses from CH1.
D1339:
For EH/EH2/SV, high word of the current number of output pulses from CH1.
D1340:
For EH/EH2/SV, settings of the first start frequency and the last end frequency of CH0.
D1343:
For EH/EH2/SV, settings of acceleration/deceleration time for CH0 pulse output.
D1352:
For EH/EH2/SV, settings of the first start frequency and the last end frequency of CH1.
D1353:
For EH/EH2/SV, settings of acceleration/deceleration time for CH1 pulse output.
D1375:
For EH2/SV, low word of the current number of output pulses from CH2.
D1376:
For EH2/SV, high word of the current number of output pulses from CH2.
D1377:
For EH2/SV, low word of the current number of output pulses from CH3.
D1378:
For EH2/SV, high word of the current number of output pulses from CH3.
D1379:
For EH2/SV, settings of the first start frequency and the last end frequency of CH2.
D1380:
For EH2/SV, settings of the first start frequency and the last end frequency of CH3.
D1348: For EH2/SV, deceleration time for CH0 pulse output when M1534 = On.
D1349: For EH2/SV, deceleration time for CH1 pulse output when M1535 = On.
D1350: For EH2/SV, deceleration time for CH2 pulse output when M1536 = On.
D1351: For EH2/SV, deceleration time for CH3 pulse output when M1537 = On.
D1381: For EH2/SV, settings of acceleration/deceleration time for CH2 pulse output.
D1382: For EH2/SV, settings of acceleration/deceleration time for CH3 pulse output.
D1383: For EH2/SV, the time difference between the direction signal and pulse output sent by CH2.
D1384: For EH2/SV, the time difference between the direction signal and pulse output sent by CH3.