9 Application Instructions API 150-199
DVP-PLC Application Manual
9-92
3. Monitor the segment No. that is currently being executed in register D301.
D0 D300
END
X0
4. The pulse output curve:
Frequency (Hz)
t
t
t
t
1
2
....
60
(D1,D0)
(D3,D2)
(D239,D238)
(D5,D4)
(D237,D236)
....
....
(D7,D6)
Time (S)
Remarks:
1. Flag explanations:
M1029
On when CH0 (Y0) pulse output is completed.
M1030
On when CH1 (Y2) pulse output is completed.
M1036
On when CH2 (Y4) pulse output is completed.
M1037
On when CH3 (Y6) pulse output is completed.
M1334
When On, CH0 (Y0) pulse output will be forbidden.
M1335
When On, CH1 (Y2) pulse output will be forbidden.
M1520
When On, CH2 (Y4) pulse output will be forbidden.
M1521
When On, CH3 (Y6) pulse output will be forbidden.
M1336
CH0 (Y0) pulse output indication flag
M1337
CH1 (Y2) pulse output indication flag
M1522
CH2 (Y4) pulse output indication flag
M1523
CH3 (Y6) pulse output indication flag
2. Special register explanations:
D1336, D1337
Pulse present value register of CH0 (Y0) (D1337 high word, D1336 low word)
D1338, D1339
Pulse present value register of CH1 (Y2) (D1339 high word, D1338 low word)
D1375, D1376
Pulse present value register of CH2 (Y4) (D1376 high word, D1375 low word)
D1377, D1378
Pulse present value register of CH3 (Y6) (D1378 high word, D1377 low word)