8 Application Instructions API 100-149
DVP-PLC Application Manual
8-55
API Mnemonic Operands Function
143
DELAY
Delay Instruction
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices Word Devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
* * *
DELAY, DELAYP: 3 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S: delay time (unit: 0.1ms)
Explanations:
1. Range of S: K1 ~ K1,000. See the specifications of each model for their range of use.
2. After DELAY instruction is executed, the program after DELAY in every scan period will execute delay outputs
according to the delay time designated by the user.
Program Example:
When X0 goes from Off to On and generates an external interruption, the interruption subroutine will execute DELAY
for 2ms before executing the next step, X1 = On and Y0 = On.
M1000
DELAY
K20
FEND
I001
X1
Y0
IRET
END
EI
REF Y0 K8
Main Program
Output Y0
T=2ms
Input X1
Interrupt input X0
Remarks:
1. User can define the delay time based on their needs.
2. The delay time may increase due do the influences from communication, high-speed counters and high-speed
pulse output instructions.
3. The delay time of designated external output (transistor or relay) will increase due to the delay on the transistor